符合最新的GB3906-2006,IEC62271-200及DL/T 404-2007等标准。
模块化紧凑型设计。
配用3AE-SION断路器(固封/普通真空断路器两种)及3TL61F/65F型真空接触器-熔断器组合电器。
标准化、人性化设计,易操作、易维护。
全面解决方案,灵活的安装方式,可满足不同客户的需求。
西门子质量体系保证,高可靠性。
Designed according to the latest standards of GB3906,IEC62271,DL/T 404.
Module structure and compact design.
3AE-SION(AP/EP)integration and with 3TL61F/65F CFC.
Standardized and humanized design guarantees the easy operation and convenient maintenance.
Versatile solutions and flexible ways of installation to meet the different requests of customers.
High reliablity from the SIEMENS quality guarantee system.
额定电压
Rated Voltage
kV
12
额定频率
Rated frequency
Hz
50
额定短时工频耐受电压(相间,对地及断口间)
Rated power-frequency withstand voltage, to earth and between phases / Across isolating distance
42/48
额定雷电冲击耐受电压(相间,对地及断口间)
Rated lightening impulse withstand voltage, to earth and between phases / Across isolating distance
75/85
额定短路开断电流
Rated short-circuit breaking current
kA
25,31.5,40
额定短时耐受电流,最大
Rated short time withstand current
kA/s
40/4
额定短路关合电流,最大
Rated short-circuit making current
100
额定母线电流
Rated busbar current
A
1250;2500;3150;4000
馈线电流
Rated feeder current
内部燃弧故障等级
Internal arc fault classification
IAC
25kA/1s;31.5kA/1s;40kA/1s
产品标准
Design and testing standard
GB3906 / IEC62271 / DL/T404
典型方案
Typical Solution
断路器柜,隔离柜,母联柜,计量柜,接触器柜,上进上出柜等